Welcome to Lvneng Electricity Technology Co.,Ltd.
|  Version:中文版English

PVC Insulated Cable for House Wiring

PVC Insulated and Sheathed Cables for Fixed Wiring

PVC Insulated and Sheathed Cables for Fixed Wiring

    Share:

1. Standard

IEC 60227, GB/T 5023


2. Application

This product is used in fixed power transmission lines of rated voltage 300/500V and below.

3. Guide to Use
Max permissible working temperature of cable conductor for long-term operation is70℃ Max. conductor temperature in normal use: 70℃


4. Code, Description and Specifications

Code Descrtion Rated Voltage (V) No. of Cores Sectional Area (mm2)
60227 IEC 10 (BVV) Light duty PVC sheathed cable 300/500 2, 3, 4, 5 1.5~35

5. Technical Particulars
No. of Cores * Sectional Area
(mm2)
Conductor Strands Insulation Thickness
(mm)
Sheath Thickness
(mm)

Max. Overall Diameter
(mm)

Approx. Weight

(kg/km)

Max. Conductor DC Resistance at 20

(Ω/kM)

Min. Insulation Resistance
(Ω/kM)
Plain Copper Tinned Copper
2*1.5 1 0.7 1.2 10.0
84.9 12.1 12.2 0.011
2 0.7 1.2 10.5
89.1 12.1 12.2 0.010
2*2.5 1 0.8 0.9 11.5
116.9 7.41 7.56 0.010
2 0.8 1.2 12.0
124.8 7.41 7.56 0.009
2*4 1 0.8 1.2 12.5
154.0 4.61 4.70 0.0085
2 0.8 1.2 13.0 162.4 4.61 4.70 0.0077
2*6 1 0.8 1.2 13.5 201.4 3.08 3.11 0.0070
2 0.8 1.2 14.0 211.7 3.08 3.11 0.0065
2*10 1 1.0 1.2 16.5 342.8 1.83 1.84 0.070
2 1.0 1.4 17.5 354.1 1.83 1.84 0.065
2*16 2 1.0 1.4 20.0 481.2 1.15 1.16 0.052
2*25 2 1.2 1.4 24.0 717.8 0.727 0.734 0.050
2*35 2 1.2 1.6 27.5 955.5 0.524 0.529 0.0044
3*1.5 1 0.7 1.2 10.5 105.8 12.1 12.2 0.011
2 0.7 1.2 11.0 110.8 12.1 12.2 0.010
3*2.5 1 0.8 1.2 12.0 149.3 7.41 7.56 0.010
2 0.8 1.2 12.5 159.0 7.41 7.56 0.009
3*4 1 0.8 1.2 13.0 201.0 4.61 4.70 0.0085
2 0.8 1.2 13.5 211.1 4.61 4.70 0.0077
3*6 1 0.8 1.4 15.5 278.6 3.08 3.11 0.010
2 0.8 1.4 17.5 291.5 3.08 3.11 0.009
3*10 1 1.0 1.4 17.5 457.6 1.83 1.84 0.0070
2 1.0 1.4 19.5 472.4 1.83 1.84 0.0065
3*16 2 1.0 1.4 21.5 652.8 1.15 1.16 0.0052
3*25 2 1.2 1.4 26.0 985.1 0.727 0.734 0.0050
3*35 2 1.2 1.6 29.0 1316.4 0.524 0.529 0.0044
4*1.5 1 0.7 1.2 11.5 129.9 12.1 12.2 0.011
2 0.7 1.2 12.0 137.0 12.1 12.2 0.010
4*2.5 1 0.8 1.2 13.0 185.9 7.41 7.56 0.010
2 0.8 1.2 13.5 199.7 7.41 7.56 0.009
4*4 1 0.8 1.4 14.5 264.0 4.61 4.70 0.0085
2 0.8 1.4 15.0 280.0 4.61 4.70 0.0077
4*6 1 0.8 1.4 16.0 352.2 3.08 3.11 0.0070
2 0.8 1.4 17.0 372.1 3.08 3.11 0.0065
4*10 1 1.0 1.4 19.0 589.3 1.83 1.84 0.0070
2 1.0 1.4 20.5 614.2 1.83 1.84 0.0065
4*16 2 1.0 1.4 23.5 848.1 1.15 1.16 0.0052
4*25 2 1.2 1.6 27.5 1309.6 0.727 0.734 0.0050
4*35 2 1.2 1.6 32.0 1724.1 0.524 0.529 0.0044
5*1.5 1 0.7 1.2 12.0 155.0 12.1 12.2 0.011
2 0.7 1.2 12.5 163.6 12.1 12.2 0.010
5*2.5 1 0.8 1.2 14.0 223.9 7.41 7.56 0.010
2 0.8 1.2 14.5 240.8 7.41 7.56 0.009
5*4 1 0.8 1.4 16.0 319.0 4.61 4.70 0.0085
2 0.8 1.4 17.0 338.3 4.61 4.70 0.0077
5*6 1 0.8 1.4 17.5 428.2 3.08 3.11 0.0070
2 0.8 1.4 18.5 452.4 3.08 3.11 0.0065
5*10 1 1.0 1.4 21.0 721.0 1.83 1.84 0.0070
2 1.0 1.4 22.0 750.1 1.83 1.84 0.0065
5*16 2 1.0 1.6 26.0 1063.1 1.15 1.16 0.0052
5*25 2 1.2 1.6 31.5 1612.3 0.727 0.734 0.0050
5*35 2 1.2 1.6 35.0 2127.7 0.524 0.529 0.0044

Other Products

  • Non-sheathed Cables for Fixed Wiring

  • Copper and Aluminum conductor PVC Insulated Cables for Fixed Wiring

  • PVC Sheathed Flexible Cables

  • PVC Insulated Twisted Flexible Cable

  • PVC Sheathed Screened Flexible Cable

  • PVC Insulated Nylon Sheathed Building Wire

  • Flame retardant nylon jacket line